Horn bills 1000 & 2000

Horn bills 1000 & 2000 Static switch have different user selectable parameters with DSP control. It is excellent performance enhancement system useful for Data center, Process Automation, Power plant, Healthcare, Telecom, Broadcasting, Industry type of environment. Natural air cooled for highest reliability

Static Transfer Switch Horn bills 1000 & 2000

Features & Benefits

  • 32 bit DSP controllers
  • Automatic instantaneous transfer and retransfer without cross connection of sources
  • Interlocking of hardware & software to avoid make – before switching
  • Enhanced monitoring and diagnostics
  • RS 232 or RS 485 interface with MODBUS protocol
  • Redundant power supply
  • 19″ Rack mountable
  • Complies with IEEE 446
  • Natural air cooled for highest reliability

Technical Specification(Horn bills 1000 & 2000)

INPUT / OUTPUT
Nominal Voltage 110 / 115/230 / 240 VAC (1 Ph + N)
Voltage Tolerances +/- 15%
Frequency Tolerances wide band 40 – 70 Hz Auto Selectable
Power Capacity 16A / 32A / 63A
No. of Switching Poles SINGLE TWO
Overload Capacity 110% for 1 hour, 150% for 60 s, 200% for 10 s, 1000% for 100 ms
Duty Continuous
Load Power Factor range 0.2 to unity leading or lagging
Source Voltage Distortion > 10% THD
Controller 32 bit DSP
SWITCH
Transfer < 5 ms in sync & No sync
Voltage regulation ± 2%
Retransfer < 5 ms in sync & No sync
Manual Bypass Provided
Efficiency (Ref. IEC 60146-1-1)* ≥ 99% ≥ 98%
ENVIRONMENTAL
Operating Temperature 0 to 40°C
Storage Temperature 0 to 70°C
Relative Humidity Up to 95% (Non Condensing)
Acoustic Noise @1 m (Ref. ISO 3746) ≤ 45 dBA
Altitude
PHYSICAL
Enclosure Protection IP – 20
Cooling Natural
Color RAL 7016
Cable Entry Back
Dimensions 3 U (485 x 450 x 132 mm)
Installation 19” Rack Mountable
USER INTERFACE
Indications Source 1 Healthy, Source 1 Priority, Source 1 Feeding, Source 1 Manual bypass ON, Output ON
Source 2 Healthy, Source 2 Priority, Source 2 Feeding, Source 2 Manual bypass ON, No Sync
Fault Indication Overload
Standards IEC 62310-1, IEEE 446
Other Features RS 485 MODBUS, Ethernet connectivity (optional)