Static transfer Hornbill 3000 have different user selectable parameters with DSP control. It is excellent performance enhancement system for useful in Data centers, Process Automation, Power plants, Healthcare, Telecom,broadcasting, Industry type of environment.
HORNBILL 3000
Features & Benefits
- 32 bit DSP based design
- Automatic instantaneous transfer and retransfer without cross connection of sources
- Enhanced monitoring and diagnostics
- RS 232 or RS 485 interface with MODBUS protocol
- 128 x 64 Graphics display
- Metering : Current, Voltage and Frequency
- Redundant power supply
- Redundant fans for cooling
- Inrush current limiting (optional)
- Complies with IEEE 446
Technical Specification ( static transfer Hornbill 3000 )
Nominal Voltage | Nominal Voltage | |||
Voltage Tolerances | +/- 15% | |||
Frequency Tolerances | 50 – 60 Hz(Auto selectable) | |||
Power Capacity | 63 A | 100 A | 200 A | 300 A |
No. of Switching Poles | THREE | |||
Overload Capacity | 110 % for 1 hour, 150 % for 1 min., 200 % for 10 sec., 1000 % for 100 ms | |||
Duty | Continuous | |||
Load Power Factor Range | 0.2 to Unity leading or lagging | |||
Source Voltage Distortion | < 10 % THD | |||
SWITCH | ||||
Transfer | < 5 ms | |||
Retransfer | < 5 ms | |||
Manual Bypass | Provided | |||
ENVIRONMENTAL | ||||
Acoustic Noise @ 1m (Ref. ISO 3746) | ≤ 55 dBA | ≤ 58 dBA | ||
Operating Temperature | 0 to 40 °C | |||
Storage Temperature | 0 to 70 °C | |||
Relative Humidity | Up to 95 % (Non Condensing) | |||
Altitude | ||||
Physical | ||||
Enclosure Protection | IP – 20 | |||
Cooling | Forced Air | |||
Colour | RAL 7016 | |||
Cable Entry | Bottom | |||
Dimensions (mm) W x D x H | 600 x 450 x 1000 | 800 x 500 x 1500 | ||
Installation | Free standing, floor mounted | |||
User Interface | ||||
Indications | Source 1 Healthy, Source 1 Priority, Source 1 Feeding, Source 1 Manual bypass ON, Output ON Source 2 Healthy, Source 2 Priority, Source 2 Feeding, Source 2 Manual bypass ON, No Sync |
|||
Fault Indication | Overload | |||
Display | 128 x 64 Graphics Display | |||
Metering | Source 1 & Source 2 – Voltage, Current, Frequency, Output Voltage, Output Current | |||
Standards | 128 x 64 Graphics Display | |||
Communication | ||||
Interface & Protocol | RS 232 | |||
Available Options | RS 485 MODBUS, Ethernet connectivity |