All Microtek Product Ranges are specially designed for the User’s Benefit.

Model NM72MX3KK11-IB
Rated Capacity 3 KVA / 2700 Watts
  • High Frequency and Double Conversion Online Technology.
  • High End IGBT Based.
  • High End Micro Controller Based.
  • Wide Input Voltage Range
  • Advanced PFC Technology
  • Advanced Battery Management
  • Automatic Battery Charging in UPS Off Mode
  • Short Circuit and Overload Protection
  • Smart RS232 Communication with monitoring software
  • SNMP Card Slot (Optional)
  • Over Temperature Protection.
  • EMI / RFI Noise Filter
  • LCD/LED Display simultaneously
  • Specially designed to suit Indian Power and Environment Conditions
  • Generator Compatible (Supplying Sinewave Voltage)
  • Isolation Transformer (Optional)
  • Different Output Voltage settings.
  • Output Frequency fixed at 50Hz or can be synchronized with Input Frequency.
  • Static Bypass Enable or Disable.
  • Outlets Programmable and Non Programmable.
  • Protection from DC Fan failure.
  • In-built Over Voltage Cut-Off Device.
WEIGHT 28.900 kg
WEIGHT 28.900kg
DIMENSIONS (L W H) 560x320x460
INPUT
Input Voltage Range (Load < 50%) 118 ~ 295 V (± 5 V)
Input Voltage range ((Load > 50%)) 160 ~ 295 V (± 5 V)
Frequency 40 ~ 70 Hz
Phase Single Phase with Ground
Power Factor ≥ 0.99 @ full load
BATTERY
DC Voltage 72 V(6* 7.0 AH Battery inside)
Charge Current 1.5 Amps
Communication Interface RS232,SNMP (Optional)
Indication LCD Display
Noise Level Less than 50dBA @ 1 Meter (With Fan Speed Control)
UPS Overload / UPS Short-Circuit 110% / 300%
Warranty One Year

NOTE: Product Specifications are subject to change without prior Notice.

OUTPUT
Voltage Range 208 / 220 / 230 / 240 V AC
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Battery Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
THD (Linear Load) ≤ 2%
THD (Non Linear Load) ≤ 4%
Overload > 110%, 30s turn to Bypass Mode
  > 150% instant turn to Bypass
Crest Factor 3:1 (Max)
Short Circuit Protection 5 cycles turn Off Inverter, no transfer to Bypass, provide Alarm (AC Mode), 5 cycles turn Off Inverter, provide Alarm(Battery Mode), Input Fuse blown or Breaker action
Waveform Pure Sinewave
Transfer time
(AC Mode to Battery Mode)
(Inverter to Bypass Mode)
Zero
< 4 ms
Efficiency 85%~ 92%