All Microtek Product Ranges are specially designed for the User’s Benefit.
Model |
NM72MX3KK11-IB |
Rated Capacity |
3 KVA / 2700 Watts |
- High Frequency and Double Conversion Online Technology.
- High End IGBT Based.
- High End Micro Controller Based.
- Wide Input Voltage Range
- Advanced PFC Technology
- Advanced Battery Management
- Automatic Battery Charging in UPS Off Mode
- Short Circuit and Overload Protection
- Smart RS232 Communication with monitoring software
- SNMP Card Slot (Optional)
- Over Temperature Protection.
- EMI / RFI Noise Filter
- LCD/LED Display simultaneously
- Specially designed to suit Indian Power and Environment Conditions
- Generator Compatible (Supplying Sinewave Voltage)
- Isolation Transformer (Optional)
- Different Output Voltage settings.
- Output Frequency fixed at 50Hz or can be synchronized with Input Frequency.
- Static Bypass Enable or Disable.
- Outlets Programmable and Non Programmable.
- Protection from DC Fan failure.
- In-built Over Voltage Cut-Off Device.
WEIGHT |
28.900 kg |
WEIGHT |
28.900kg |
DIMENSIONS (L W H) |
560x320x460 |
INPUT |
Input Voltage Range (Load < 50%) |
118 ~ 295 V (± 5 V) |
Input Voltage range ((Load > 50%)) |
160 ~ 295 V (± 5 V) |
Frequency |
40 ~ 70 Hz |
Phase |
Single Phase with Ground |
Power Factor |
≥ 0.99 @ full load |
BATTERY |
DC Voltage |
72 V(6* 7.0 AH Battery inside) |
Charge Current |
1.5 Amps |
Communication Interface |
RS232,SNMP (Optional) |
Indication |
LCD Display |
Noise Level |
Less than 50dBA @ 1 Meter (With Fan Speed Control) |
UPS Overload / UPS Short-Circuit |
110% / 300% |
Warranty |
One Year |
NOTE: Product Specifications are subject to change without prior Notice.
OUTPUT |
Voltage Range |
208 / 220 / 230 / 240 V AC |
Frequency Range (Synchronized Range) |
47 ~ 53 Hz or 57 ~ 63 Hz |
Frequency Range (Battery Mode) |
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
THD (Linear Load) |
≤ 2% |
THD (Non Linear Load) |
≤ 4% |
Overload |
> 110%, 30s turn to Bypass Mode |
|
> 150% instant turn to Bypass |
Crest Factor |
3:1 (Max) |
Short Circuit Protection |
5 cycles turn Off Inverter, no transfer to Bypass, provide Alarm (AC Mode), 5 cycles turn Off Inverter, provide Alarm(Battery Mode), Input Fuse blown or Breaker action |
Waveform |
Pure Sinewave |
Transfer time
(AC Mode to Battery Mode)
(Inverter to Bypass Mode) |
Zero
< 4 ms |
Efficiency |
85%~ 92% |